If Option 8 is ON, the 'Z/P' terminal is an
output.
If Option 8 is OFF, the 'Z/P' terminal is an
input.
Programming the PGM Number
In order to assign a PGM output to the "Z/P"
terminal, a PGM number must be entered.
This number has to be one of the PGM out-
puts that can be programmed in the panel.
1. Enter [
][8] [Installer Code].
2. Enter [000] to go to Keypad Program-
ming.
3. Enter Section [8].
4. Enter the 2-digit PGM number (01-14).
AC Icon (PC5020 only)
The AC icon displays the AC is present at
the main panel. You can program the
LCD5511 to either go out or flash when
the AC is not present.
1. Enter [
][8] [Installer Code]
2. Enter [000] to go to Keypad Program-
ming.
3. To select the desired operation for the
AC icon, enter section [6].
4. Turn Option [4] On or Off:
ON = AC Icon flash on loss of power
OFF = AC icon not displayed on loss of
power
5. When you are finished, press [#] to exit.
Trouble Icon
The Trouble icon is displayed when a
system trouble is active.
Low Temperature Warning
The keypad zone can be alternatively pro-
grammed to be a low temperature warn-
ing instead of a physical zone input. If
programmed, the zone will go into alarm
o
o
at 6
C (+/-2
) and restore at 9
1. Enter [
][8] [Installer Code].
2. Enter [000] to go to Keypad Program-
ming.
3. Enter section [7].
4. Enable or disable the low temperature
warning by pressing [8].
ON = Low temperature warning enabled
OFF = Low temperature warning disabled
NOTE: Only 1 of 3 options may be selected for
the input/output terminal (Zone, PGM or Low
Temperature).
5
o
o
C (+/-2
).