3.0 venting requirements
venting requirements
EN
WARNING
!
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring assembly
WARNING
!
W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both
vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air
gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
elbow to ensure this gap is maintained. These spaces must not be removed.
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring assembly
W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the section
vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air
applicable to your installation.
gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each
elbow to ensure this gap is maintained. These spaces must not be removed.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical
vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the section
minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that
applicable to your installation.
pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve
to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical
installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several
minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for
pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve
400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is recommended.
to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is
note:
installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for
installation.
400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is recommended.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate
constructions, such as a chimney as part of the vent system, is not permitted.
note:
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial
Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp venting components. Minimum and
installation.
You may reduce the appliance from 5/8" venting to 4/7" venting for horizontal and vertical rise applications.
maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate
Reducing must be done right off of the appliance and a new firestop spacer will be required.
terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Metal-Fab, BDM, Simpson
constructions, such as a chimney as part of the vent system, is not permitted.
Dura-Vent, or Selkirk Direct Temp, follow the installation procedure provided with the venting components or on the website
for your venting supplier.
Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp venting components. Minimum and
A starter adaptor must be used with the following vent systems and may be purchased through Wolf Steel or from the
maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air
corresponding supplier listed below:
terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Metal-Fab, BDM, Simpson
Dura-Vent, or Selkirk Direct Temp, follow the installation procedure provided with the venting components or on the website
for your venting supplier.
Venting System
A starter adaptor must be used with the following vent systems and may be purchased through Wolf Steel or from the
corresponding supplier listed below:
SureSeal
Direct Vent Pro
Venting System
Pro-Form
SureSeal
Direct Temp
Direct Vent Pro
Ventis
Pro-Form
Connections made by means of an adaptor at the appliance, as well as the connection at the vent terminal must be sealed.
Direct Temp
RTV sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems, ex-
cept for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature
Ventis
sealant Mill Pac.
Connections made by means of an adaptor at the appliance, as well as the connection at the vent terminal must be sealed.
For all vent systems is strongly recommend for all installations but required when power venting the appliance, that the outer
RTV sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems, ex-
air intake joints are sealed using either high temperature silicone (RTV) or a suitable aluminum tape that covers each joint in
cept for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature
the vent system entirely around its circumference. This will ensure the best performance in every application and avoids per-
sealant Mill Pac.
formance or condensation concerns that may occur in "tightly" constructed homes, particularly those in cold climates.
For all vent systems is strongly recommend for all installations but required when power venting the appliance, that the outer
air intake joints are sealed using either high temperature silicone (RTV) or a suitable aluminum tape that covers each joint in
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on
the vent system entirely around its circumference. This will ensure the best performance in every application and avoids per-
termination shape (i.e. round, or round and square). See appropriate templates folder.
formance or condensation concerns that may occur in "tightly" constructed homes, particularly those in cold climates.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on
termination shape (i.e. round, or round and square). See appropriate templates folder.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
10
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
W415-4051 / C / 06.29.22
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
be combined.
Starter Adapter
Manufacturer
Part Number
Metal-Fab
5DNA
Starter Adapter
Simpson DuraVent
W175-0170
Manufacturer
Part Number
BDM
N/A
Metal-Fab
5DNA
Selkirk
5DT-AAN
Simpson DuraVent
W175-0170
Olympia Chimney
VDV-NA05-58F
BDM
N/A
and Venting
Selkirk
5DT-AAN
Olympia Chimney
VDV-NA05-58F
and Venting
Supplier
Wolf Steel
Wolf Steel
Supplier
BDM
Wolf Steel
4DNA
Selkirk
W175-0053
Wolf Steel
Olympia Chimney
DVR6-STA7
BDM
and Venting
4DT-AAN
Selkirk
Olympia Chimney
and Venting
Website
www.mtlfab.com
www.duravent.com
Website
www.dalsinmfg.com
www.mtlfab.com
www.selkirkcorp.com
www.duravent.com
www.olympiachimney.com
www.dalsinmfg.com
www.selkirkcorp.com
www.olympiachimney.com