Radio channel. (Only available through wired thermostat). This allows you to enable/disable
the system's wireless association channel.
Note: When the radio channel is opened, it will remain open for 15 minutes.
•
Away mode settings. (Only available through Airzone Cloud). This option allow you to
configure the parameters of the Unoccupied user mode and the Vacation user mode:
1.
Hysteresis. If the set point temperature is surpassed by the differential defined, the zone
will cease demand. Range: 1 to 3,5 ºC / 2 to 7 ºF in steps of 0,5 ºC / 1 ºF (by default 3 ºC / 6
ºF).
2.
Override time (min). Sets time (in minutes) that the zone will resume the selected away
mode when the user touches the thermostat screen during an away period. Values: 10 to
120 minutes in steps of 10 minutes. By default, 60 minutes.
•
Auxiliary heat. (Only available through Airzone Cloud). This allow you to enable/disable the
auxiliary heat. By default, the auxiliary heat is disabled. When auxiliary heat is enabled, the
following parameters need to be configured:
1.
Configuration menu
o Available stages. Defines how many stages of auxiliary heat a system has (1 or 2).
o First supply heat. Select the first system to supply heat: Heat pump or Auxiliary heat.
o Fan configuration. Select between Electric (fan on) or Furnace (fan off) option. If you
select Electric option, define:
- Fan delay (s). Defines the delay time (in seconds) to turn off the fan when there is no
demand from the Auxiliary heater. Values: 0, 45, 60 and 120 seconds.
2.
First stage menu
o First stage differential.
to surpass to activate the first stage of auxiliary heat. Values: 1 to 5 ºC / 2 to 10 ºF, in
increments of 1 ºC / 2 ºF (by default, 1 ºC / 2 ºF).
o First stage hysteresis. Defines the hysteresis for the operation of the first stage. Values:
0,5 to 1 ºC / 1 to 2 ºF, in increments of 0,5 ºC / 1 ºF (by default 0,5 ºC / 1 ºF).
o Min. time exhausted. Defines the minimum time (in minutes) that the first supply
heat must be active before the first stage of auxiliary heat can be activated. Values: 0, 45,
60 and 120 minutes. By default, 45 minutes.
Defines the temperature differential that the system has