Radio channel. (Only available through wired thermostat). This allows you to enable/disable
the system's wireless association channel.
Note: When the radio channel is opened, it will remain open for 15 minutes.
Away mode settings. (Only available through Airzone Cloud). This option allow you to
configure the parameters of the Unoccupied user mode and the Vacation user mode:
1.
Hysteresis. If the set point temperature is surpassed by the differential defined, the zone
will cease demand. Range: 1 to 3,5 ºC / 2 to 7 ºF in steps of 0,5 ºC / 1 ºF (by default 3 ºC / 6
ºF).
2.
Override time (min). Sets time (in minutes) that the zone will resume the selected away
mode when the user touches the thermostat screen during an away period. Values: 10 to
120 minutes in steps of 10 minutes. By default, 60 minutes.
Auxiliary heat. (Only available through Airzone Cloud). This allow you to enable/disable the
auxiliary heat. By default, the auxiliary heat is disabled. When auxiliary heat is enabled, the
following parameters need to be configured:
1.
Configuration menu
o Available stages. Defines how many stages of auxiliary heat a system has (1 or 2).
o First supply heat. Select the first system to supply heat: Heat pump or Auxiliary heat.
o Fan configuration. Select between Electric (fan on) or Furnace (fan off) option. If you
select Electric option, define:
- Fan delay (s). Defines the delay time (in seconds) to turn off the fan when there is no
demand from the Auxiliary heater. Values: 0, 45, 60 and 120 seconds.
2.
First stage menu
o First stage differential.
to surpass to activate the first stage of auxiliary heat. Values: 1 to 5 ºC / 2 to 10 ºF, in
increments of 1 ºC / 2 ºF (by default, 1 ºC / 2 ºF).
o First stage hysteresis. Defines the hysteresis for the operation of the first stage. Values:
0,5 to 1 ºC / 1 to 2 ºF, in increments of 0,5 ºC / 1 ºF (by default 0,5 ºC / 1 ºF).
o Min. time exhausted. Defines the minimum time (in minutes) that the first supply
heat must be active before the first stage of auxiliary heat can be activated. Values: 0, 45,
60 and 120 minutes. By default, 45 minutes.
Defines the temperature differential that the system has