System advanced settings
EN
AIRZONE BLUEFACE ZERO
Press and hold
System parameters
•
System address. (Not available on systems with BACnet gateway). This allows you to define
the number of the system in your installation.
•
Temperature range (Stages). (Only available through Airzone Cloud). This allows you to
select the maximum temperature for heating mode (18 – 30 °C / 64 – 86 ºF, by default 30 °C /
86 ºF) and minimum temperature for cooling mode (18 – 26 °C / 64 – 78 ºF, by default 18 °C /
64 ºF), in steps of 1 °C / 2 ºF. If you want, you can disable any of the modes.
•
Global ventilation. (Only available through Airzone Cloud). This allow you to activate/
deactivate the fan mode in all zones when the system is not actively heating or cooling
any zones. By default, the global ventilation is deactivated. When activated, the following
settings have to be configured:
1.
Every (min). Configure the length of the interval (in minutes) between periods of
activation of global ventilation. Configurable from 5 to 40 minutes, in 5 minutes
increments (by default, 15 minutes).
2.
Run for (min). Configure the time duration (in minutes) that global ventilation is
activated. Configurable from 5 to 20 minutes, in 5 minutes increments (by default, 10
minutes).
Note: When global ventilation is activated, a warning message will appear on the
screensaver.
•
Type of opening. This allows you to enable/disable the proportionality of the system
dampers. Proportionality scales the opening or closing of the damper in 4 steps according
to the temperature demand of the zone, adjusting the zone airflow rate. By default, it is set
to Modulating.
If you select the Modulating option, select the desired damper and set the REG lever
position, where position I is completely open.