POWER SUPPLY TO THE SYSTEM
Use power supply input to power the main
control board at 110/230  VAC as well as
any other control elements that require
external power supply. Use 3x1.5 mm²
EN
(3x0.023 in
) cable. To supply power to the
2
main control board, loosen the cable gland
if necessary, insert the cable through the
hole (Ø: 5 - 10 mm [0.2 - 0.4 in]) and attach
the cables to the terminal following the
polarity indicated. Connect the terminal
to the power supply input and tighten the
cable gland to attach the power supply
cable.
The connection to the external power
supply must include a main switch, or
other
method
of
disconnection,
that
includes a constant separation for all
polarities, in accordance with appropriate
local and national regulations. The system
will automatically restart if the power
supply is turned off. Use separate circuits
for the unit that is to be controlled and the
power supply to the system.
Once all the connections have been made,
make sure the cover of the main control
board is correctly replaced.
Note: If you need more information about the system installation or configuration, please refer
to the Installation Manual.