AIRZONE THINK
EN
Remember: To access the main screen from the wireless thermostat screensaver, press
on Airzone.
•
Associated outputs. (Not available on systems with BACnet gateway). This displays and
allows you to select the control outputs associated to the thermostat.
•
Use mode. This allows you to configure the thermostat for the system's different zones
in Basic or Advanced mode. By default, it is set to Advanced. The parameters that can be
controlled in Basic mode are:
- On/Off.
- Set point temperature.
- Operation mode (only if this is the master thermostat).
- Fan speed.
If you need to reset the thermostat to Advanced mode, access the Advanced settings menu
and activate Advanced use mode.
•
Offset. This allows you to correct the room temperature measured in the different zones or
in all of them, due to deviations produced by sources of heat/cold nearby, with a correction
factor between - 2,5 °C / - 5 ºF and 2,5 °C / 5 ºF in steps of 0,5 °C / 1 ºF. By default, it is set to 0
°C / 32 ºF.
•
Weight. This option is used to set the weight of each zone for purposes of determining
system operation. The weight of the zone will be used for calculating the mode (auto-
change over) or for calculating heat demands when using auxiliary heat. Options: Auto or
Manual.
o Auto. (By default). The weight of each zone is automatically assigned based on the
number of zones.
o Manual. Enables to manually define the weight of each zone. Values: 0 to 100.
•
Reset thermostat. (Not available in remote zones). This allows you to reset the thermostat
by returning to the initial settings menu.
22
Press and
hold
Press and
hold