Troubleshooting
Troubleshooting
Note:
Additional help
14
All manuals and user guides at all-guides.com
Use the table below to localise and correct problems or errors:
Problem
• Dehumidifier will not
start
• Display not switched on
• Dehumidifier will not
start
• Green light not on
• HYG STOP shown on
display
• Red light on
• Dehumidifier running
• Green light on
• SERVICE flashing on
display
• Dehumidifier running
• When RH% activates,
the display shows SEN-
SOR FAIL
• kWh and hours without
power not displayed
• If the machine is not working properly, switch off immediately!
• Before starting troubleshooting, wait for one minute, as the electronics could have
cut off the machine for safety reasons
If the dehumidifier will not restart, contact your Dantherm dealer. This also applies if the
machine runs without condensing any water. There may be a fault on the cooling circuit
which will require a service technician
www.dantherm-ltd.ru • info@dantherm-ltd.ru • +7 (495) 545-48-79
Москва. Каширский проезд д. 19 стр. 2
Possible cause
Plug not in mains socket
The hygrostat has meas-
ured air humidity lower
than the set point, and
switched off to save power
Error stopping the machine See user guide table on
Service interval set has ex-
pired
RH% sensor defective
Memory battery flat.
Solution
Check dehumidifier is con-
nected to the mains. Check
the mains socket if neces-
sary by connecting another
electrical appliance
Reduce hygrostat set point,
or switch to manual opera-
tion. See the section on In-
ternal hygrostat operation
page 7
page 9on error messages
Service the product as
specified in the section on
service counter expiry
Replace RH% sensor
Replace battery. See page 9