TECHNICAL DATA
TYPE
Output - Thermal power
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC Directives: EMC 2014/30/UE, Low Voltage
2014/35/UE, Machines 2006/42/EC .
The burner meets protection level of IP 40, EN 60529.
9
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
2094
463 M
4.5 – 9 kg/h
-
Light oil, max. viscosity at 20 °C: 6 mm
Single phase, 230 V ± 10%
50 Hz – Run current 0.75 A – 2785 rpm – 292 rad/s
60 Hz – Run current 0.75 A – 3340 rpm – 349 rad/s
4 F
Secondary 8 kV – 16 mA
Pressure: 7 – 15 bar
0.17 kW
Fig. 1
7
6
6
10
D8070
7 – Air-damper
8 – Combustion head adjustment screw
9 – Lock-out lamp and reset button
10 – Flange with insulating gaskets
1
GB
54 – 107 kW
2
/s
~
50Hz
2
ENGLISH
8
1
5