Mounting and Installation
DE
US
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
Separating "intrinsically safe circuits" from "non-intrinsically-safe circuits"
KR
CN
20
SolConeX
Receptacle, 30 A
8571/21 series
Explosion hazard in the case of installation in special dust hazardous
areas!
Non-compliance results in severe or fatal injuries.
• Do not use the device in areas where there are processes
generating strong charges, machine friction processes,
separation processes and electrospray processes
(e.g. around electrostatic coating systems)
and pneumatically generated dust.
Explosion hazard if seal is insufficient and/or service temperature
is too high!
Non-compliance results in severe or fatal injuries.
• Completely seal the bayonet ring of the plug and of the hinged
cover to obtain the degree of protection.
• Securely seal and lock the enclosure.
• Make sure the service temperature range is maintained
(see the "Technical data" chapter).
Two conductors can be installed under one connection terminal.
The conductor material and conductor cross-section of both conductors must
be identical.
The conductors can be connected without any special prior measures.
• 6 mm/0.24 inch for a peak nominal voltage ≤ 375 V
• 8 mm/0.31 inch for a peak nominal voltage ≤ 750 V
• or with earthed shielding in accordance with UL 913 or UL 60079-11,
UL 60079-25 (sufficient current load capacity)
DANGER
DANGER
294386 / 8571661300
2022-08-08·IO00·III·en·00