Mounting auxiliary contacts
For mounting instructions for installing the auxiliary contacts,
see installation note 8570/8571 (8570607300).
7.3
Installation
Explosion hazard due to insufficient protective measures!
Non-compliance results in severe or fatal injuries.
• Select suitable conductors to ensure that the maximum
• Lay cables in intrinsically safe circuit separately to cables in
• When using core end sleeves, attach them using a suitable tool.
• Use only separately tested cable entries and stopping plugs
• The conductor insulation must be touching the terminal.
• Do not damage the conductor (e.g. nicking)
• Always connect the protective conductor.
294386 / 8571661300
2022-08-08·IO00·III·en·00
permissible conductor temperatures are not exceeded.
non-intrinsically-safe circuits. The distance measurements for
this can be found in the "Separating intrinsically safe circuits
from non-intrinsically-safe circuits" section.
with a US EC Type Examination Certificate.
when stripping it.
Mounting and Installation
• Open the enclosure.
• Snap the auxiliary
contacts into place
optionally in the left-hand
or right-hand seat.
Double equipping is
possible.
• Close the enclosure.
11203E00
DANGER
SolConeX
Receptacle, 30 A
8571/21 series