Technical Data; Flue - Nordica VERONA XXL Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

TECHNICAL DATA

Definition in accordance with
Nominal power in kW
Assorbimento elettrico in W
Efficiency in %
smoke outlet diameter in mm
Chimney height ≥ (m) - dimension (mm)
Chimney draught in Pa (mm H
Hourly wood consumption in kg / h
CO measured at 13% oxygen in %
Exhaust gas emission in g/s – wood
Exhaust gas temperature in °C - wood
Hearth opening size in mm (W x H)
Hearth size in mm (W x H x D)
Oven size in mm (W x H x D)
Type of grill
Height in mm
Width in mm
Depth in mm
Weight in kg
fire prevention safety distances
Heatable m
3
(30 kcal/h x m
Rated voltage (V)
Rated frequency (Hz)
Rated input power (W)
(*) The proposed value are indicative. The installation must, in any case, be sized and verified according to the general calculation method in UNI
EN13384-1 or by another method of proven efficiency.
(**) For those buildings in which the thermal insulation does not correspond to the instructions on heat protection, the heating volume of the
product is: favourable type of building (30 kcal/h x m
x m
).
3
With thermal insulation in accordance with the regulations regarding energy saving, the heated volume is greater. With temporary heating, in
the event of interruptions which last more than 8 hours, the heating capacity is reduced by about 25%.
THE DECLARED TECHNICAL DATA HAVE BEEN ACHIEVED BY BURNING BEECH WOOD CLASS "A1" ACCORDING TO THE REQUIREMENT UNI EN ISO
17225-5 AND WOOD MOISTURE CONTENT LESS THAN 20%. BY BURNING A DIFFERENT KIND OF WOOD THE EFFICIENCY OF THE PRODUCT ITSELF
COULD CHANGE AND SOME SPECIFIC ADJUSTMENTS ON THE APPLIANCE COULD BE NEEDED.

fLUE

ESSENTIAL REQUIREMENTS FOR CORRECT APPLIANCE OPERATION:
the internal section must preferably be circular;
• the appliance must be thermally insulated and impermeable and built with suitable materials which are resistant to heat,
combustion products and any condensation;
there must be no narrowing and vertical passages with deviations must not be greater than 45°;
if already used, it must be clean;
all the sections of the flue gas duct must be accessible to inspection;
inspection openings must be provided for cleaning.
the technical data from the instruction manual must be respected;
IF THE FLUES ARE OF A SQUARE OR RECTANGULAR SECTION, THE INTERNAL EDGES MUST BE ROUNDED WITH A RADIUS OF NOT LESS THAN 20
MM. FOR THE RECTANGULAR SECTION, THE MAXIMUM RATIO BETWEEN THE SIDES MUST BE ≤ 1.5.
A section which is too small causes a reduction in draught. A minimum height of 4 m is advisable.
The following materials are fORBIDDEN and compromise the good operation of the appliance: asbestos cement, galvanised steel, rough and
Picture 1
porous internal surfaces.
fOR A CORRECT INsTALLATION PLEAsE REsPECT THE sECTIONs/LENgTHs Of THE fLUE sHOWN IN THE TECHNICAL DATA
TABLE. BY INsTALLATIONs WITH DIffERENT DIMENsIONs THE fLUE MUsT BE sUITABLY sIZED IN ACCORDANCE WITH
EN13384-1.
THE DRAUGHT CREATED BY YOUR FLUE MUST BE SUFFICIENT BUT NOT EXCESSIVE.
A section of the flue which is too large can present a volume which is too large to heat and therefore cause operating difficulties for the
28
O)
2
(wood with 20% humidity)
)
3
); less favourable type of building (40 kcal/h x m
3
shows some example solutions.
ENGLISH
VERONA XXL
EN 12815
7
25
85,1
150
(*) 4 - 200 x 200 Ø 200
12 ( 1,2 mm H
O)
2
1,9
0,084 - 1044 mg/m
3
5,7
207
500 x 160
568 x 215 x 240
547 x 275 x 450
Movable - flat
850 - 910
800
600
175
Chapter FIRE SAFETY
200 (**)
230
50
25
); unfavourable type of building (50 kcal/h
3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Rosa xxlRosa l

Table des Matières