Fronius Primo
Input data
MPP voltage range
Initial voltage
Max. input voltage
at 1000 W/m² / 57.2°F (14 °C) in an open circuit
Nominal input voltage
Nominal input current
Max. input current
Max. short circuit current of the solar modules
Output data
Nominal output power (P
nom
P
at +131°F (55°C)
nom
Max. output power
Nominal mains voltage
Mains voltage tolerance
Operating AC voltage range
Grid voltage setting range
Voltage limit accuracy
Voltage limit clearing times setting range
Nominal output current
Number of phases
Maximum output fault current / duration at 208 V
Nominal output frequency
Output frequency range
Setups: 50Hz, 60Hz
Setup: HI1
Setting range for grid frequency
Frequency limit accuracy
Frequency clearing times setting range
Total harmonic distortion
Power factor (cos phi)
)
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 220 V
at 240 V
7.6-1 208-240
8.2-1 208-240
250 - 800 V
270 - 800 V
80 V
1000 V
660 V
12.3 A
13.3 A
(12.6 A at 208 V)
18.0 A
18.0 A
22.5 A
22.5 A
7600 W
7900 W
7600 W
8200 W
7600 W
8200 W
5300 W
5300 W
5450 W
5450 W
5550 W
5550 W
7600 W
7900 W
7600 W
8200 W
7600 W
8200 W
208 V / 220 V / 240 V
-12 % / +10 %
183 - 229 V
194 - 242 V
211 - 264 V
104 - 288 V
104 - 288 V
104 - 288 V
1% of nominal value
0.016 - 21.0 s
36.5 A
38.0 A
34.5 A
37.3 A
31.7 A
34.2 A
1
384 A / 146 ms
560 A / 172 ms
584 A / 154 ms
50 / 60 Hz
48.0 - 50.5 Hz / 59.3 - 60.5 Hz
- / 57.0 - 63.0 Hz
45.0 - 55.0 Hz / 50.0 - 65.0 Hz
0.05 Hz
0.016 - 600 s
< 5 %
1)
0.85 - 1 ind./cap..