en | Wiring
7.
Set the DIP switch according to the designated application.
You can write down the Physical Node Address (PNA) and
the IP address on the label (see 07, page 10 ).
4
Wiring
Notice!
Do not modify the fire alarm control panel to extend USB and
IN1/2 cables outside the housing. Only use cables for USB and
IN1/2 with a maximum length of 3 m.
Notice!
You will find detailed information about the CAN and Ethernet
networking of the panels in the Networking Guide available for
download at
https://www.boschsecurity.com .
Notice!
The manufacturer's specifications for the minimum bending
radius of the network and fiber optic cables used must be
observed during installation.
The panel controller features
2 CAN interfaces (CAN1/CAN2) for networking
1 Rail connector
4 Ethernet interfaces (1 / 2 / 3 / 4) for networking,
prescribed usage:
2 signal inputs (IN1/IN2)
1 USB function interface for configuration via FSP-5000-
RPS
1 Memory card interface
2020.05 | 6.0 | F.01U.347.557
All manuals and user guides at all-guides.com
1 and 2 (blue): Panel network
3 (green): Building management system, hierarchy
panel, voice alarm system
4 (red): Remote Services
AVENAR panel series
Bosch Sicherheitssysteme GmbH