LPG Kit
2
LPG kit
2.1
Kit description
The LPG kit allows the burners fitted for burning methane, to op-
erate on LPG.
All the installation, maintenance and disassembly
operations must be carried out with the electricity
supply disconnected.
DANGER
2.2
Burner equipment
Quantity
Components
5
Gas tube
5
Tube fixing screws
1
Ionisation probe
1
Flame disc
1
Diffuser
(1)
1
Label
1
Tecnical instructions
(1)
Apply the self-adhesive label for LPG operation near the char-
acteristic label.
2.3
Technical data
Model
Thermal power
Fuel
(2)
Gas pressure
(2)
Measured on the coupling with 0 mbar resistance in the com-
bustion chamber and burner maximum output.
2.4
Conversion
Close the fuel interception tap.
DANGER
For combustion head conversion (Fig. 1) replace the following
material with the standard equipment supplied:
➤ diffuser 1), flame disk 2) and ionisation probe 3);
➤ the outer tubes T1), T2) and T3) must be positioned as follows:
- tubes T1: on hole 1;
- tubes T2: on hole 5;
- tubes T3: on hole 3.
20007823
WARNING
RS 650
1.410/3.020 ÷ 6.500 kW
1.215/2.600 ÷ 5.600 Mcal/h
47,8 mbar
2
GB
The installation of the LPG kit must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
1.200/3.500 ÷ 8.000 kW
1.032/3.010 ÷ 6.880 Mcal/h
Commercial LPG
3
Ncv = 25.8 kWh/Nm
(C
H
= 93 - 94%)
3
8
3
22,200 kcal/Nm
RS 800
34 mbar