4 Applications
The circulation pumps in the PRIUX home series are designed for hot-water
heating systems and other similar systems with constantly changing volume
flows.
Approved fluids are heating water in accordance with VDI 2035, water/glycol
mixture at a mixing ratio of max. 1:1. If glycol is added, the delivery data of the
pump must be corrected according to the higher viscosity, depending on the
mixing ratio percentage.
Intended use also includes following these instructions.
Any other use is regarded as incorrect use.
5 Product information
5.1 Type key
PRIUX home 40-25/180
PRIUX
home
40
25
180
5.2 Technical data
Connection voltage
Protection class IP
Water temperatures at max. ambient
temperature of +40°C
Water temperatures at max. ambient
temperature of +25°C
Max. ambient temperature
Max. operating pressure
Min. inlet pressure at+95 °C/+110 °C
EEI
* The benchmark for most efficient circulators is EEI ≤ 0,20
5.3 Scope of delivery
• Pump + gaskets + Salmson connector.
• Installation and operating instructions.
Pompes Salmson SAS
All manuals and user guides at all-guides.com
High-efficiency pump
Residential application
Head at 0 m³/h
ND Threaded connection
Port-to-port dimension
1 ~ 230 V ± 10 %, 50/60 Hz
See name plate
–10 °C to +95 °C
–10 °C to +110 °C
–10 °C to +40 °C
6 bar
0,3 bar/1,0 bar
See name plate*