Attention: when first turned on the product executes the auto-calibration of the hygrostat. It is possible that during this
phase the "EXTRACTION" function will be activated to bring the room's humidity below the level required for this auto-ca-
libration.
Response:
Light impulse on activation of the H1 value (RH: 40%)
Light impulse on activation of the H2 value (RH: 55%)
Light impulse on activation of the H3 value (RH: 70%)
F: Direction of airflow (function can be activated if there are at least 2 units or multiple coupled units)
By pressing the "DIRECTION OF AIRFLOW" button the units generate an airflow that provides intake only and extraction
only simultaneously for the desired time, always keeping the atmosphere balanced. According to the button pressed, the
air intake and extraction direction can be reversed.
Attention: ethe sensors are not active in this function.
Attention: the speed can be modified through the V commands pressed previously to those F.
Response:
Light pulse on activating the mode
Periodic light pulse (every 1 min.) active mode
I: Air intake function
By pressing the "AIR INTAKE FUNCTION" the product intakes air. In the case of several units, all of them intake air simul-
taneously until another command is given by the user.
Attention: the sensors are not active in this function.
Response:
Light pulse on activating the mode
Periodic light pulse (every 1 min.) active mode
E: Air extraction function
By pressing the "AIR EXTRACTION FUNCTION" the product extracts air. In the case of several units, all of them extract air
simultaneously until another command is given by the user.
Attention: the sensors are not active in this function.
Respuesta:
Light pulse on activating the mode
Periodic light pulse (every 1 min.) active mode
COMMISSIONING
• Every time you turn on the RESPIRO RD (using the "0/1" switch) you have to wait 20 seconds before the unit will respond to
remote control orders.
During the first 15s, the unit is powering up. In this state the red LED is on.
Once the red LED has turned off, another 5 seconds pass until we see a white blink.
Only after flashing white will the unit respond to remote control orders.
• It is important not to press any button until we have seen the white blink, otherwise the unit could be blocked.
• The fan may take up to a minute to start as it will not start rotating until the damper is fully open.
• Every time you send an order to the RESPIRO RD, you are sure that the unit has received the order by checking that the white
LED blinks.
• Every time you unplug the unit, it returns to AUTOMATIC MODE at the next start-up.
FILTER ALARM RESET
Every 2000 hours of operation the indicator light at the bottom right will emit a continuous red light signal. The product will
continue to operate by keeping the last command received.
To reset the hour counter inside the unit, press the key sequence detailed below (refer to the image of the remote control
on page 1):
HI - HI - H2- H2- H3- H3
1 Red
2 Red
3 Red
2 Red / 3 seg. / 2 Red
Red
1 Red / 3 seg. / 1 Red
Red
1 Rojo / 3 seg. / 1 Rojo
Rojo
EN
|||
|||
|||
37