4.4
Calcification protection
Limescale deposits from the water increase significantly at higher temperatures (>55°C). Set
the temperature as low as possible for this reason.
Observe hygiene regulations!
In order to ensure the longest possible service life of the plate heat exchanger, the manufac-
turer recommends using water softeners if the water hardness level is > 8.5°dH.
Water treatment measures to prevent scale formation (water softening)
Mass concentration of calcium carbonate
[mmol/l]
< 1.5 (equivalent to < 8.4°dH)
(equivalent to < 14,95°fH)
> 1.5 to < 2.5
(equivalent to > 8.4°dH to < 14°dH)
(equivalent to > 14,95°fH to < 24,92°fH)
> 2.5 (equivalent to > 14°dH)
(equivalent to > 24,92°fH)
Refer to the Maintenance section for recommendations on cleaning the heat exchanger.
Art.-Nr. 907.75.02.00
Last updated 2022/08/29
Fresh water station with
premix function
Tapping temperature
approx. 50°C
None
None
Recommended
- 8 -
GB
Fresh water station
without premix function
Tapping temperature
approx. 60°C
None
Recommended
Required