3.3

Corrosion protection

To prevent corrosion damage to plate heat exchangers, the following drinking water values
must be observed:
1
-
Chloride
(CL
)
1
2-
Sulphate
(SO
)
4
Nitrate (NO3-)
pH value
Electrical conductivity
(at 20°C)
Hydrogen carbonate
-
(HCO
)
3
-
2-
Ratio HCO
/SO
3
4
+
Ammonia (NH
)
4
Free chlorine gas
Sulphite
Hydrogen sulphide
(H
S)
2
Free (aggressive) car-
bon dioxide (CO
)
2
Iron (Fe)
Hydrogen carbonate
-
(HCO
)
3
Saturation index SI
Manganese (Mn)
Degree of hardness
Total organic carbon
(TOC)
1
It is not permitted to use the fresh water station if the limit values are exceeded.
To prevent pitting corrosion in the domestic installation, no new galvanised iron material must
be installed downstream in the hot water pipe of the copper-soldered plate heat exchanger
without forming a protective layer.
Solid stainless steel plate heat exchangers must be used in mixed installations with zinc-
coated iron materials.
3.4

Calcification protection

Limescale deposits from the water increase significantly at higher temperatures (>55°C). Set
the temperature as low as possible for this reason.
Observe hygiene regulations!
In order to ensure the longest possible service life of the plate heat exchanger, the manufac-
turer recommends using water softeners if the water hardness level is > 8.5°dH.
For heating systems where the heating water flow temperature would often exceed 65 °C
due to the system, a thermal premix of 65 °C would be reasonable. This applies above all to
biomass systems, but also to solar thermal systems. Conversely, in heat pump heaters with
already relatively low flow temperature, it can be dispensed with the premix, which can
906.50.02.00
Last updated 2022/03/16
Copper-soldered
< 100 mg/l
< 100 mg/l
7,5 - 9,0
10 - 500 µS/cm
70 - 300 mg/l
> 1
< 2 mg/l
< 1 mg/l
< 0,05 mg/l
< 5 mg/l
< 0,2 mg/l
-0,2 < 0 < 0,2
< 0,05 mg/l
[Ca
< 30mg/l
- 7 -
Solid stainless steel
< 250 mg/l at 50°C
< 100 mg/l at 75°C
< 10 mg/l at 90°C
< 400 mg/l
No requirement
7,0 – 10,0
No requirement
No requirement
No requirement
No requirement
< 0,5 mg/l
< 7 mg/l
< 2 mg/l
No requirement
No requirement
No requirement
No requirement
No requirement
4 – 14
2+
2+
-
; Mg
]/ [HCO
] > 0,5
3
No requirement