Read this manual carefully before using the product and keep it in a safe place for reference.
This product was constructed up to standard and in compliance with regulations relating to electrical equipment and must
be installed by technically qualified personnel.
The manufacturer assumes no responsibility for damage to persons or property resulting from failure to observe the
regulations contained in this booklet.
PRECAUTIONS FOR INSTALLATION, USE AND MAINTENANCE
• The device should not be used for applications other than those specified in this manual.
• After removing the product from its packaging, verify its condition. In case of doubt, contact a qualified technician. Do
not leave packaging within the reach of small children or people with disabilities.
• Do not touch the appliance with wet or damp hands/feet.
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without supervision.
• Do not use the product in the presence of inflammable vapours, such as alcohol, insecticides, gasoline, etc.
• If any abnormalities in operation are detected, disconnect the device from the mains supply and contact a qualified
technician immediately. Use original spare parts only for repairs.
• The electrical system to which the device is connected must comply with regulations.
• Before connecting the product to the power supply or the power outlet, ensure that:
- the data plate (voltage and frequency) correspond to those of the electrical mains
- the electrical power supply/socket is adequate for maximum device power. If not, contact a qualified technician.
• The device should not be used as an activator for water heaters, stoves, etc., nor should it discharge into hot air/fume
vent ducts deriving from any type of combustion unit. It must expel air outside via its own special duct.
• Operating temperature: -20°C up to +50°C.
• The device is designed to extract clean air only, i.e. without grease, soot, chemical or corrosive agents, or flammable
or explosive mixtures.
• Do not leave the device exposed to atmospheric agents (rain, sun, snow, etc.).
• Do not immerse the device or its parts in water or other liquids.
• Turn off the main switch whenever a malfunction is detected or when cleaning.
• For installation an omnipolar switch should be incorporated in the fixed wiring, in accordance with the wiring regulations, to
provide a full disconnection under overvoltage category III conditions (contact opening distance equal to or greater than
3mm).
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
• Do not obstruct the fan or exhaust grille to ensure optimum air passage.
• Ensure adequate air return/discharge into/from the room in compliance with existing regulations in order to ensure
proper device operation.
• If the environment in which the product is installed also houses a fuel-operating device (water heater, methane stove
etc., that is not a "sealed chamber" type), it is essential to ensure adequate air intake, to ensure good combustion and
proper equipment operation.
• Install the product so that the impeller is not accessible from the air outlet side as verified by contact with the Test Finger
(test probe "B" of the norm EN61032) in compliance with the current safety regulations.
INTRODUCTION
DMV HR is a single alternate flow decentralized (single point) residential heat recovery unit, also called «push&pull» unit, designed to ensure adequate
ventilation in enclosed environments without energy losses.
It is recommended that two units are installed in pair: when one unit is pulling, the other is pushing. Pair of units can be installed in the same room or
in different rooms (i.e. livingroom and bedroom). The unit is suitable for installation on an outside wall.
The unit should operate continuously, and only stopped for maintenance or service. When heat exchange is not useful (for example in
mid-seasons when indoor and outdoor temperatures are similar), or when heat exchange is not recommended (for example with the
option "summer free cooling"), it is recommended to set the unit in "extract-only" or "intake-only" mode and NOT to switch it off.

TECHNICAL SPECIFICATIONS

• Inner ventilation unit material: high quality, impact and UV-resistant ABS colour RAL 9010.
• Design front cover removable for cleaning without the use of tools.
• Easy maintenance installation plate, for easy access to the heat exchanger from inside the room.
• Anti-dust filter, easily removable for washing by the user without tools.
• Regenerative honeycombs ceramic heat exchanger.
• External grille in high quality, impact and UV-resistant ABS colour RAL 9010.
• High efficiency aerodynamic fan with "winglet" blades to optimise quietness and efficiency.
• Single phase EC reversible Brushless motor with integral thermal protection.
• Motor mounted on high quality ball bearings.
• The unit is double insulated: no earth connection is required.
• Trickle speed selectable.
• Boost mode.
• Free-cooling (Bypass) mode.
• IPX4 degree of protection.