FLOATING ACTUATOR
BLACK
WHITE
BROWN
2
3
4
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 9. MVN613 with Floating Control.
FLOATING ACTUATOR
BLACK
WHITE
BROWN
3
2
4
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 10. MVN613 or MVN643 with Two Position SPDT
Control.
FLOATING ACTUATOR
BLACK
WHITE
BROWN
3
2
4
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
Fig. 11. MVN643 with Two Position SPST Control.
VRN DYNAMIC PRESSURE-REGULATING CONTROL VALVES AND ACTUATORS
1
24 VAC
2
FLOATING
CONTROLLER
M33137D
1
24 VAC
2
FLOATING
CONTROLLER
M33138C
1
24 VAC
SPST
M33557C
PROPORTIONAL/MODULATING: 4-20mA CONTROLLER OUTPUT WITH
500Ω SERIES RESISTOR
PROPORTIONAL ACTUATOR
DIP SWITCH POSITION
1
2
MODE
OFF
OFF
2-10V
OFF
ON
0-10V
ON
OFF
10-2V
ON
ON
10-0V
RED
BLACK
WHITE
500 OHMS,
1/2 W
MINIMUM
+
1
2
3
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 12. MVN713 with 4-20mA Control.
PROPORTIONAL/MODULATING: 0(2)...10 VDC OR 10...0(2) VDC CONTROLLER OUTPUT
PROPORTIONAL ACTUATOR
DIP SWITCH POSITION
1
2
MODE
OFF
OFF
2-10V
OFF
ON
0-10V
ON
OFF
10-2V
ON
ON
10-0V
+
1
2
3
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
Fig. 13. MVN713 with 0(2)-10 Vdc Control.
5
24 VAC
TO OTHER
ACTUATORS
+
4-20mA
CONTROLLER
2
RED
BLACK
24 VAC
WHITE
+
0 (2)-10 VDC
CONTROLLER
38-00005EFS—04
1
M33141C
1
M33140A