VRN DYNAMIC PRESSURE-REGULATING CONTROL VALVES AND ACTUATORS
Table 1. Close-off, Differential Pressure Ratings.
Valve Type
Valve Size
2 way
1/2 in. to 3 in.
INSTALLATION
When installing this product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for your appli-
cation.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.

Preparation

CAUTION
Equipment Damage Hazard
Foreign particles like dirt and metal chips can
damage the ball seals.
For trouble-free operation of the product, good
installation practice must include initial system
flushing, and chemical water treatment. Clean the
lines upstream of particles larger than 1/16 inch
diameter (welding slag, pipe scale, sand and other
suspended particulate). Use of a 50 micron (or
finer) system side stream filter is suggested.
Remove all filters before flushing.
Do not use boiler additives, solder flux and wetted
materials which are petroleum based or contain
mineral oil, hydrocarbons, or ethylene glycol
acetate. Compounds which can be used, with
minimum 50% water dilution, are diethylene
glycol, ethylene glycol, and propylene glycol
(antifreeze solutions).
If installing these valves in an addition to, or
retrofitting an existing building, do not assume
that the fluid in the existing piping meets these
criteria.

Mechanical Installation

IMPORTANT:
Hold valve with pipe wrench by hexagonal fitting
ONLY. Do NOT handle the valve body with the pipe
wrench; product damage may result.
38-00005EFS—04
The valves are tapped in NPT and should be sealed with an
approved pipe sealant. Torque should not exceed 75 lb-ft.
Refer to actuator literature for actuator dimensions.
Close-off
Pressure Rating
(psi)
100
IMPORTANT
2
1. Clean the lines upstream of particles larger than
1/16 in. diameter (welding slag, pipe scale and other
contaminants).
2. Proceed with installation once the system specifics
(expansion/contraction of the system and its
medium as well as operating pressures) are within
tolerances.
3. Eliminate air from system.
4. Valves are marked to show flow direction.
Flow arrows must point in the direction of the flow
for proper operation.
5. Stem rotation:
a. Clockwise to close.
b. Counterclockwise to open.
NOTE: After valves have been installed in the pip-
ing, the installer can determine the ball ori-
entation within the valve from the notches
in the top of the valve stem. For VRN valves,
the lengthwise direction of the notch indi-
cates the flow through the ball (i.e. when the
notch is parallel to the axis of the valve
between A and B ports, the ball will allow
flow through the valve).
6. Valve must be mounted with the actuator/bracket
above the valve body. Do not install the valve with
the stem below horizontal or upside down. (See
Fig. 3 and 4.)
FLOW
OPEN
NOTES: TO MOUNT ACTUATOR ON OPEN VALVE, TURN ACTUATOR FULLY
COUNTER CLOCKWISE AS SHOWN. TO MOUNT ACTUATOR ON
CLOSED VALVE, TURN ACTUATOR FULLY CLOCKWISE AS SHOWN.
Fig. 1. Orientation of valve.
FLOW
CLOSED
M34979A