Honeywell V8043C Guide Rapide

Honeywell V8043C Guide Rapide

Vannes de zones motorisées

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

APPLICATION:
The V8043 Motorized Zone Valve provides two-position
(open-close) control of supply water for baseboard radiation,
convectors, fan-coil units, etc. It uses a two-wire, 24-volt con-
trol circuit and requires a SPST thermostat. Integral end-switch
models permit the sequencing of auxiliary equipment.
FEATURES:
Quiet, dependable operation is provided by motor-operated
powerhead and swing-type ball valve.
Unique rotating ball plug that seats on a different part of its
surface on each closing.
Closes against the flow of water to assure quiet operation.
Manual opener moves ball away from seat allowing valve
to be installed without disassembly.
Manual operation on power failure.
Easy servicing because the entire powerhead assembly can
be replaced without removing valve body from line. Op-
tional accessory fittings can be provided to facilitate con-
venient removal of the entire zone valve unit.
Low power requirements allow four valves to be operated
from a single 40 VA transformer.
Integral end-switch on F & G models to permit sequencing
of auxiliary equipment.
Choice of sweat, female NPT and flare (with union-flare
adapters) body styles.
Compact construction permits fitting under cover of
most baseboards,
SPECIFICATIONS:
MODELS:
V8043C - Normally closed
V8043D - Normally open
V8043F - Normally closed with integral line voltage end
switch
V8043G - Normally closed with integral low voltage end
switch
BODY STYLES:
All models have straight through pattern only.
1/2", 3/4" or 1'' sweat or female NPT, or 3/8" flare.
Inlet fittings can be provided with or without 1/16''
diameter bypass or bleed.
CLOSE-OFF WATER PRESSURES AND CAPACITY (CV)
RATINGS:
All models - 50 psi for 1.0 Cv
20 psi for 3.5 Cv (Standard Rating)
8 psi for 8.0 Cv
STATIC PRESSURE RATING:
Both 125 psi (VC8043C/D/F/G1000 series) and
300 psi (V8043C/D/G3300 series) models available
TEMPERATURE RATING:
o
o
Liquid -
4
C to 93
C (40
Ambient - 4
o
C to 52
o
C (40
Steam -
Consult your local Honeywell representative
WIRING CONNECTIONS:
'C' and 'D' Models - 2 low voltage 0.5 m (18 in.) leadwires
with strain relief
'F' Tradeline Model - 5 screw terminal board. Includes
'blind' terminal for transformer and thermostat wiring
convenience. (See Fig. 4) It Also includes add-on line
voltage enclosure with conduit opening for end switch
wiring.
'G' Model - 4 low voltage 0.5 m (18 in.) leadwires with
strain relief.
POWER REQUIREMENTS AND TIMING:
All models - 24 V, 50/60 Hz (cycles) 6 W nominal, 15
seconds to open, and 4-5 seconds to close.
Order transformer separately. See alternate selection.
www.honeywell.ca/water-controls/
o
o
F to 200
F)
o
F to 125
o
F)
V8043C, D, F & G
MOTORIZED ZONE VALVES
V8043C, D
V8043G
TRANSFORMER:
All models - AT72 or AT20B (maximum of 4 valves per
AT72 or 2 valves per AT20B).
Order transformers separately.
AUXILIARY SWITCH RATINGS:
'G' Model - 50 VA pilot duty at 24 Vac
'F' Model - 4.4 Amps running at 120 Vac
RECOMMENDED WALL THERMOSTATS:
Heating Only - T86A, T822D:
(T822C for normally open [N.O.] valves)
Cooling Only, or Heating-Cooling - T87F with Q539
THERMOSTAT HEATER SETTING:
For Heat Anticipation: 0.32 Amps
REPLACEMENT POWERHEADS:
125 psi Models:
'C' Model - P/N 40003916-011
'D' Model - P/N 40003916-014
'G' Model - P/N 40003916-012
'F' Model - P/N 40003916-013
REPLACEMENT MOTOR:
24 Vac, 50/60 Hz Models - P/N 272748AB
24 Vac, 50/60Hz, Plated Motor - P/N 272748ABP
REPLACEMENT END SWITCH:
Old Style (prior to 1978) requiring metal bracket
- P/N 272744A
New Style - P/N 272744B
REPLACEMENT 0-RING: P/N 272756A
NOTE
The standard valve is not recommended for steam service.
Consult you local Honeywell representative whenever steam
applications are involved.
ACCESSORIES:
Flare-to-Sweat Union Adapters (sold in sets of 2)
3/8 Flare to 1/2 Sweat - P/N 272704A
3/8 Flare to 3/4 Sweat - P/N 272704B
Residential & Building Controls Group
V8043F
272704A
95C-10002B-1

Publicité

loading

Sommaire des Matières pour Honeywell V8043C

  • Page 1 ‘C’ Model - P/N 40003916-011 STATIC PRESSURE RATING: ‘D’ Model - P/N 40003916-014 Both 125 psi (VC8043C/D/F/G1000 series) and ‘G’ Model - P/N 40003916-012 300 psi (V8043C/D/G3300 series) models available ‘F’ Model - P/N 40003916-013 TEMPERATURE RATING: REPLACEMENT MOTOR: Liquid -...
  • Page 2 TERMINAL BOARD SWEAT FNPT 3/8 FLARE Clearance necessary to cover removal Flair-to-sweat union adapter Dimensions for Fig. 1 in mm (inches in brackets) MODELS V8043C, D, G 60 (2 79 (3 22 (7/8) 19 (3/4) 98 (3 ) 87 (3 7/16...
  • Page 3 Steam applications require special ball plugs. Consult ing temperature it requires. your local Honeywell representative. WIRING: All wiring must conform to local electrical codes and ordinances. Refers to Fig. 4 to 7 for wiring connections. Fig. 5 - V8043G WIRING Fig.
  • Page 4 The valve will return to automatic position when the valve is energized. Automation and Control Solutions Home and Building Control Environmental Control Products Honeywell Limited-Limitee 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN, USA Toronto, ON, Canada...
  • Page 5: Caractéristiques

    Modèle G – Quatre fils conducteurs basse tension de 0,5 m Une vanne ordinaire n’est pas recommandée pour les applications [18 po] avec serre-câble. à vapeur. Consulter un représentant Honeywell dans le cas d’applications à vapeur. CARACTÉRISTIQUES ÉLECTRIQUES ET TEMPORISATION : Tous les modèles –...
  • Page 6 ENTRÉE SORTIE NFPT 3/8 ÉVASÉ Espace nécessaire pour enlever le couvercle Adaptateur union évasé-à souder Dimensions de la Fig. 1 en mm [po] MODÈLES V8043C, D, G 60 (2 79 (3 22 (7/8) 19 (3/4) 98 (3 87 (3 7/16...
  • Page 7: Montage

    à vapeur, il faut utiliser des obturateurs sphériques à l’argent en raison de sa température de fusion élevée. spéciaux. Consulter un représentant Honeywell. CÂBLAGE : Tout le câblage doit être conforme aux codes d’électricité et aux règlements locaux. Se reporter aux figures 4 à 7 pour les schémas de raccordement.
  • Page 8: Fonctionnement

    MAN. OPEN*. La vanne revient à la position marche automatique lorsqu’elle est mise sous tension. Solutions de régulation et d’automatisation Produits de régulation d’ambiance Honeywell Inc. Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive...

Ce manuel est également adapté pour:

V8043dV8043fV8043g