ALARMS
ALARM CODE
Description
1
Memory write error
2
Water Input Probe Broken or Disconnected
3
Water Output Probe Broken or Disconnected
4
Outside Air Probe Broken or Disconnected
5
Battery Probe Broken or Disconnected
6
Discharge Probe Broken or Disconnected
7
Intake Probe Broken or Disconnected
8
AP Transducer Broken or Disconnected
9
BP Transducer Broken or Disconnected
10
Super-heating alarm low (EVD)
11
LOP Alarm (EVD)
12
MOP Alarm (EVD)
13
Condensation Temperature Alarm (EVD)
14
Intake Low Temperature Alarm (EVD)
15
Valve Alarm (EVD)
16
Valve Auto-Tuning (EVD)
17
Emergency Valve Closure (EVD)
18
Range Error Alarm (EVD)
19
Pin Out of Limit Value Valve Alarm
20
Flow Meter Alarm
21
Anti-freeze alarm
22
Pump Magneto-Thermal Alarm
23
Low Pressure Alarm
24
High pressure alarm
25
Serious Low Pressure Alarm
26
Fan Magneto-Thermal Alarm
27
High force gas temperature:
28
Faulty cycle inversion valve: Low deltaP. The reverse cycle valve could be faulty or blocked
29
Delta P higher than allowed at start up (default = 20bar). Does not cause machine block
30
ForceOff Compressor
31
Operating Limit Time Exceeded Alarm
32
Compressor start-up failed. Does not cause machine block
33
Pressure differential lower than specified value (0.3 bar in 60sec)
34
Over-current
35
Compressor motor overload
36
DC BUS over-voltage
37
DC BUS under-voltage
38
Driver over-temperature
39
Drive under-temperature
40
Hardware over-current
41
Compressor over-temperature
42
IGBT module error – Internal fault. Replace Inverter
43
CPU error
44
Default parameters
45
DC bus ripple. Check phase voltages powering the inverter
46
No communication between inverter and uPC3
47
Drive temperature sensor fault
48
Auto-configuration failed
49
Inverter drive not enabled. Check bridges on Power Plus Inverter terminal strip
50
Motor phase error
51
Inverter cooling fan faulty
52
Speed fault. Compressor stalled. Check type of compressor set
53
PFC fault (alarm occurs with PFC enabled while DC bus is very low)
54
PFC overload trip (this alarm will no longer be included in new versions of the firmware)
55
Input voltage error (when power supply falls below 170 V with the motor running)
56
STO 1 error
57
STO 2 error
58
Ground/Earth connection fault (only for single-phase)
59
Internal error 1 (ADC conversion sync fault)
60
Internal error 2 (Hw sync fault)
14