It has a 4-pin terminal to connect the thermostat. Use the proper cable: shielded twisted pair 4 wired:
2 +
2
2x0.22 mm
2x0.5mm
(AWG 20 4 wired). Attach the wires with the terminal screws following the color
code (Fig. 17).
Remember: The maximum separation between the module and the thermostat is 40 meters.
The zoning module allows you to connect a probe (AZZBS10KPROBE) for remote or distributed temperature reading,
depending on how the module is configured:
Remote probe: This function allows you to read the room temperature even if you are not where the thermostat is
located. Connect the probe and configure the module as main module (connected thermostat). The state and the set-
point temperature are set via thermostat while the set-point temperature is set via probe.
Distributed probe: This function allows you to control a subordinate zone with room temperature reading independent
from the main zone. Connect the probe and configure the module as
and the set-point temperature are set via thermostat while the set-point temperature is set via probe.
The module has several inputs to control based on the occupancy or if there are open windows.
Control by occupancy: When the occupancy sensor connected to the module indicates that the zone is unoccupied,
the system waits for 5 minutes to confirm it is actually empty. After this period of time, the zone is set to Timer Mode
and it turns off after 90 minutes.
Control by open window: When the open window sensor connected to the module indicates that a window is open
for more than 60 seconds, the control element (actuator/relay) associated with that module closes.
The activation and configuration of these inputs are available in the zone settings menu of the thermostat (see Advanced
Configuration).
WIRED/WIRELESS ZONE MODULE WITH XXX COMMUNICATION (AZZBSZM XXX [C/R])
Fig. 18
Assembly
The module is mounted on DIN rail (Fig. 19) or on wall (Fig. 20). It must be placed and mounted in accordance with the current
electrotechnical regulations.
N
Description
Probe Input
Window contact
Presence contact
Thermostat Connection
Airzone Connection Bus
Note: Use a shielded twisted pair to connect the window contact.
(
connected thermostat). The state
(Only AZZBSZMxxxC)
Fig. 17
20