E1016 & E1018
PANEL MOUNT RECEPTACLES
Installation and Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Eaton Cam-Lok connectors are designed to meet
NEC Code requirements for listed connectors that
are of the locking type. These single pole plugs
and receptacles are insulated in a specially for-
mulated elastomeric material for water tightness
and safety. They allow you to connect or discon-
nect electrical equipment instantly without tools.
Cam-Lok connectors are the industry standard for
motors, generators, indoor and outdoor lighting
INSTALLATION
Note: Use Copper (CU) Conductors Only.
Male/Female Double Set Screw Panel Mounts:
1. Remove cable jacket.
* Cut 1-5/8" for double set screw contacts
2. Wrap cable with copper shim.
3. Wrap strain relief wire.
IM 1039
Copyright © 2018, Eaton Corporation.
distribution panels, and numerous other power
applications.
Cam-Lok E1016 & E1018 series connectors are
rated at 600 Volts up to 400 Amperes Continu-
ous. Actual operation must comply with the infor-
mation stipulated in the unit's nameplate.
4. Prepare panel per cut out below:
Attach receptacle to panel using four (4) #10-24
screws with nuts and lock washers (not provided).
6. Insert cable into contact.
7. Tighten screws using 7/32" Hex Wrench.
Male/Female Threaded Stud:
IM 1039
1.
Prepare cable and crimp lug per
manufacture's requirements.
*Cable lugs vary depending on cable size (not
provided).
2. Attach lug to threaded stud using 1/2" flat
washer and 1/2 –13 UNC hex nut (not provided).
Tighten nut to 40 ft. lbs.
5.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable.
The accuracy or completeness thereof are not guaranteed. In accordance with Eaton's "Terms and Conditions of Sale," and since condi-
tions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk
and liability whatsoever in connection therewith.
Page 1
OPERATION
1. To mate, fully engage male to female and rotate
1/3 of a turn clockwise.
2. To unmate, rotate male counter clockwise 1/3
of a turn and pull straight out.
MAINTENANCE
Perform visual, electrical and mechanical checks
of all components on a regular
should be determined by the environment and
frequency of use, but it is recommended that it
should be at least once per year.
Eaton.com/recycling
Eaton Corporation
Crouse-Hinds Division
4758 Washington Street, LaGrange, NC 28551 USA
Copyright © 2018, Eaton Corporation
schedule. This
REV C:
IC-ECN004493

Publicité

loading

Sommaire des Matières pour Eaton Crouse-Hinds Serie

  • Page 1 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton’s “Terms and Conditions of Sale,” and since condi- tions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Page 2 Eaton Corporation REV C: Crouse-Hinds Division IC-ECN004493 4758 Washington Street, LaGrange, NC 28551 USA Copyright © 2018, Eaton Corporation IM 1039 Copyright © 2018, Eaton Corporation. Page 1...

Ce manuel est également adapté pour:

E1016E1018