Response example:
01 04 D8
53FDAEF0 05FC 0000 05FB 0000 05FA 0000 05FB 0000 002E 0000 002D 0000 0030 0000 002F 0000
53FDAF2C 0955 0000 0953 0000 0953 0000 0954 0000 003C 0000 003C 0000 003F 0000 003D 0000
53FDAF68 10BB 0000 10B9 0000 10B8 0000 10BA 0000 0057 0000 0057 0000 005B 0000 0059 0000
53FDAFA4 10C4 0000 10C2 0000 10C1 0000 10C2 0000 0057 0000 0057 0000 005B 0000 0059 0000
53FDAFE0 10BF 0000 10BD 0000 10BC 0000 10BE 0000 0057 0000 0058 0000 005C 0000 0059 0000
53FDB01C 10C1 0000 10BF 0000 10BE 0000 10BF 0000 0057 0000 0058 0000 005C 0000 0059 0000
A26C
Example Byte Description
01
-
Slave address
04
-
Function code
D8
-
216 data bytes
53
High
FD
Low
27
th
AE
High
F0
Low
05
High
0,111 kW phase 1 imported active power AVG (+P1
FC
Low
00
High
0 kW phase 1 exported active power AVG (-P1
00
Low
05
High
0,111 kW phase 2 imported active power AVG (+P2
FB
Low
00
High
0 kW phase 2 exported active power AVG (-P2
00
Low
05
High
0,111 kW phase 3 imported active power AVG (+P3
FA
Low
00
High
0 kW phase 3 exported active power AVG (-P3
00
Low
05
High
0,333 kW system imported active power AVG (+P∑
FB
Low
00
High
0 kW system exported active power AVG (-P∑
00
Low
00
High
0,003 kvar phase 1 imported reactive power AVG (+Q1
2E
Low
00
High
0 kvar phase 1 exported reactive power AVG (-Q1
00
Low
00
High
0,003 kvar phase 2 imported reactive power AVG (+Q2
2D
Low
00
High
0 kvar phase 2 exported reactive power AVG (-Q2
00
Low
00
High
0,003 kvar phase 3 imported reactive power AVG (+Q3
30
Low
00
High
0 kvar phase 3 exported reactive power AVG (-Q3
00
Low
00
High
0,010 kvar system imported reactive power AVG (+Q∑
2F
Low
00
High
0 kvar system exported reactive power AVG (-Q∑
00
Low
53
High
FD
Low
27
th
AF
High
2C
Low
09
High
0,173 kW phase 1 imported active power AVG (+P1
55
Low
A2
High
CRC
6C
Low
66
August 2014, 10:12:00 record block
August 2014, 10:13:00 record block
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
)
AVG
1
RECORD
ST
2
RECORD
ND
MODBUS RTU/ASCII