5. READING COMMAND EXAMPLES
In this chapter, some reading command examples are described.
These tables refer to a master-slave communication in MODBUS RTU.
Values contained both in Query and Response messages are in hex format.
CURRENT VALUE READING
Query example: 0103000E000A0EA4
Example Byte Description
01
-
Slave address
03
-
Function code
00
High
Starting register
0E
Low
00
High
10 words to be read
0A
Low
0E
High
CRC
A4
Low
Response example: 010314000009990000099F000009900000001900000998C070
Example Byte Description
01
-
Slave address
03
-
Function code
14
-
20 data bytes
00
High
00
Low
2457 mA phase 1 current (A1)
09
High
99
Low
00
High
00
Low
2463 mA phase 2 current (A2)
09
High
9F
Low
00
High
00
Low
2448 mA phase 3 current (A3)
09
High
90
Low
00
High
00
Low
25 mA neutral current (AN)
00
High
19
Low
00
High
00
Low
2456 mA system current (A∑)
09
High
98
Low
C0
High
CRC
70
Low
62