12. Setting aid for mechanical pressure switches
To use the HMG 510 as a setting aid for mechanical pressure switches,
you need:
Pressure transmitter on channel A (e.g. HDA 4748-H)
E
Mechanical pressure switch on channel B
To facilitate connection of the mechanical pressure switch to the power
supply, we recommend using the UVM 3000 universal adapter.
12.1 Connection diagram
Now connect the mechanical
pressure switch to the HMG 510 as
shown in the diagram on the right:
1. Connect the pressure transmitter to
channel A.
(The pressure transmitter must
be located in the same pressure
circuit as the mechanical pressure
switch.)
2. Connect the UVM 3000 universal
adapter to channel B.
3. Connect the switching output of the
mechanical pressure switch to
ports 1 and 3 of the UVM 3000.
48
Mechanical pressure switch
HDA4748-H
Hydraulic
pressure unit
UVM3000
HMG 510