If the LED R
rotation is detected.
20
If the LED L
detected.
TIP: When re-testing with exchanged test probes the opposite
result has to be shown.
The function of this test may not be fully achieved if the
insulation condition / grounding conditions of user and/or of
the equipment under test is not good enough.

Current Measurement (A) TRMS

Warning:
W
Store test probes safely to avoid any unintended connection.
• Press ON/OFF/Function button repeatedly until LCD
shows A symbol.
• Currents between 0.1 A and 200 A can be measured.
• The wire needs to be positioned in the center of the open
jaw at the height of the markings to the left and right.
Improper placing of the wire will result into higher
measurement error.
Note: Tester will switch automatically to voltage
measurement if voltage of >6 V is detected via test leads.
Resistance Measurement (Ω)
W
The test circuit/object shall be de-energized before
measurement.
• Check for the absence of voltage by conducting a two-
pole voltage test on the test object.
• Switch into resistance measurement by pressing ON/
OFF/Function button repeatedly until Ω symbol is shown
on LCD.
• Connect both test probes to the test object. The tester
indicates the resistance digitally on the LCD screen
For very low resistances below 20 Ohms the continuity
buzzer is also active.
Tester switches to voltage measurement if voltage
>15 V or single pole is detected.
Non Contact Cable Break Detector / EF (Electric Field)
The non contact cable break detector / EF is a perfect feature
to locate the exact position of the fault location of a broken
phase conductor.
The display function of the non contact cable break
detector / EF may be impaired e.g. by insulating personal
protective equipment or at insulated locations.
W
This function is not suitable to test for absence of
voltage. This always requires a two-pole voltage test.
• Press ON/OFF/Function button repeatedly until LCD will
show "EF
• Hold the voltage tester with the sensor towards the cable
or wire to be tested. The voltage tester indicates the
strength of the signal digitally on the LCD screen.
Note: Store test probes safely to avoid any unintended
connection. Tester switch to voltage measurement if voltage
>6 V or single pole is detected between test probes.
Voltage Mode "<10V": 1V...1000VAC/1500VDC
• Press ON/OFF/Function button repeatedly until LCD
shows "<10V" symbol.
• In "Voltage Mode <10V" it is possible to measure AC and
DC voltage down to 1V.
• Connect both probes to the object under test.
• Voltage is displayed the same way as during regular
voltage measurement. Continuity mode is disabled in
"Voltage Mode <10V".
The single-pole phase test function is disabled in
"Voltage Mode <10V".
20
is constantly constantly ON - right phase
is constantly ON - left phase rotation is
".
8
6
.