achieve a higher bulk performance.
Refer to the Maintenance section for recommendations on cleaning.
Water treatment measures to prevent scale formation (water softening)
Calciumcarbonat-Massenkonzentration
< 1,5 mmol/l (< 150 mg/l)
< 8,4°dH (≙ 14,95°fH)
1,5 to 2,5 mmol/l (150 mg/l bis 250 mg/l)
8,4°dH bis 14°dH (≙14,95°fH bis 24,92°fH)
> 2,5 mmol/l (>250 mg/l)
> 14°dH (≙24,92°fH)
It should be noted that decalcification by means of ion exchange does not reduce the con-
ductivity. For this reason, use a full stainless steel exchanger from 500 µS/cm. It can roughly
be calculated that 14° dH corresponds to a conductivity of 14° dH * 35 = 490 μS/cm. Thus,
as a precaution, a full stainless steel exchanger must be used. In addition, fresh water
stations must be grounded so that no current flow over the plate heat exchanger or the piping
is performed.
4
A s s e m b l y
4.1
Assembly valve
4.1.1
Free-flow valve
906.50.02.00
Last updated 2022/03/16
Fresh water station with 50 °C hot
water outlet temperature and
flow < 65 °C
None
None
Recommended
- 8 -
GB
flow > 65 °C
None
Recommended
Recommended