Step 4. If it displays "L2", then BUZZER will be sound for twice.
Please switch the Red test lead to connect to the
supposed phase Line 2 immediately before the " L2 "
is disappeared.
Step 5. When "L2" is disappeared, it will display the testing
result.
a. If it displays " 1 2 3 ", then the phase sequence is forward
sequence, which means the supposed phase Line 1 is
ahead of the supposed phase Line 2.
b. If it displays " 3 2 1 ", then the phase sequence is reversed
sequence, which means the supposed phase Line 2 is
ahead of the supposed phase Line 1.
c. "----" means that the meter is unable to determine the
results.
d. If displays "LoU", it is possible that you remove the test
leads before completing the whole testing procedures.
Step 6 : To repeat the test, press the OK button again.
M35X6BF-M-00
18