LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous area
T4: -40 ≤ Ta ≤ 85ºC
T6: -40 ≤ Ta ≤ 60ºC
Module 5331D, 5333D
Terminal: 3,4,5,6
Only passive, or non-energy
storing devices such as RTD's
and Thermocouples may be
connected
Module 5335D, 5336D and 5337D
Terminal: 3,4,5,6
Uo: 9.6 VDC
Io: 28 mA
Po: 67.2 mW
Lo: 35 mH
Co: 2.5μF
CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations
Class I, Division 1, Groups A, B, C and D
Ex ia IIC, Ga
CLASS 2258 84 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous
Locations - Certified to US Standards
Class I, Division 1, Groups A, B, C and D
Class I, Zone 0, AEx ia IIC, Ga
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC) or for US the National Electrical Code (NEC).
Revision date:
2014-03-31
22
CSA Installation drawing 533XQC03
5335V 11 5 -FR
WWW.PRELECTRONICS.COM
6
+
1
5
-
2
4
3
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF
Version Revision
V4R0
5335QE01
Non Hazardous Area
Barrier
Page:
7/9