Wiring the device
Earthing of internal System 9400 EMC filters
Devices in the range 145 ... 245 A (75 ... 130 kW)
6.2.1
Devices in the range 145 ... 245 A (75 ... 130 kW)
Proceed as follows to disconnect the internal connection between the filters and PE:
1. The bridge 0 that connects the filter with the protective earth can be found at the
indicated position.
2. Loosen both screws 1 (do not remove them).
3. Fold the bridge 0 downwards clockwise by 90°.
4. Tighten both screws 0.
– Starting torque: 3.4 Nm (30 lb−in)
100
l
94ITSW8001
EDK94SH366 DE/EN/FR/ES/IT 7.0