Fm Installation Drawing - PR electronics 9410 Manuel De Produit

Masquer les pouces Voir aussi pour 9410:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK
9410 Power Control Unit
For safe installation of 9410 the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Non Hazardous Area or Division 2 / Zone 2
T4: -20 ºC <Ta < +60ºC
91 92 93 94 95
Status
24 V
GND
Revision date:
2019-04-04
18

FM Installation drawing

34
Backup -
33
Backup +
32
Supply +
31
Supply -
14
13
NC
12
COM
11
NO
9410
Power
Rail
Version Revision
V3 R0
9410 - Version de produit 9410-001
Terminal 34-33
Backup: 21,6 VDC – 26,6VDC / 4ADC
Terminal 31-32
Supply: 21,6 VDC – 26,6VDC / 4ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250VAC, 2A, 500VA / 30VDC, 2A, 60W
Zone 2 installation:
32VAC, 2A, 64VA / 30VDC, 2A, 60W
Prepared by:
PB
9410QF01
Page:
1/3

Publicité

Table des Matières
loading

Table des Matières