420010922100 Multicalor 70 ÷ 140 PR/AB
EN
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
The adjustment of the com-
bustion head position is car-
ried out in order to
obtain the best combustion
efficiency. When installed for
small output operations,
the head shall be adjusted back.
For maximum operation the position is fully forward.
Steps: loosen the locking screw of A lever. Move the lever to
the needed position. Tighten back the locking screw.
The burners are produced with connections suitable for power supply 380-400 V three-phase.
The burners with electric motors of an output lower or equal to 3 kW can be adapted to 220-230 V (please follow the
instructions on the backside); motors with higher output can only work 380-400 V three-phase.
In case of request of burners different from the above mentioned standard, it is recommended to make specific mention
in the order.
Instructions: how to adapt electric motors of an output lower or equal to 3 kW to 220-230 V power supply
It is possible to change the voltage of the burner by operating as follows:
1. change the connection inside the electric box of the motor, from star to delta (see picture);
2. change the setting of the thermal relay, referring to the absorption values indicated in the motor nameplate. If
FLAME DETECTOR SYSTEM CHECK
ADJUSTING THE FIRING HEAD
A

DESCRIPTION OF CONTROL PANEL

8
GAS
OIL
0
AUTO
I
0
0
SW = BLACK
BL = BLU
min.
max.
MULTICALOR
45-70-100
REMOVING THE BLAST TUBE
1
1 - Fuse
2
2 - Termal lock-out lamp
3 - Light-oil working lamp
7
3
4 - Gas working lamp
4
5 - Selector :
5
0
Loking of devoices for operating at intermediate outputs
6
Operation at max. output
Operation at min. output
AUTO
Automatic operation
6 - Main switch I / O
7 - Selector : 0 / Light-oil / Gas
8 - Lockout disable push button
pag.20
SW
1
LME22
2
BL
BL
QRA
SW
min.
max.
A
MULTICALOR
140