POSITION OF IGNITION ELECTRODES
NOZZLE CLEANING AND REPLACEMENT
F
SAL
HLBT
0
1
0: OFF
R
1: ON
HLoil
0=STOP
SAMA
1=UP
V
2=LOW
3=AUTO
B
HLgas
0=STOP
SAgG
1=OIL
R
2=GAS
3=AUTO
SA s.r
3 ÷ 4 mm
Use only the suitable box wrench provided for this operation to
remove the nozzle, taking care to not damage the electrodes. Fit the
new nozzle with the same care.
Note: Always check the position of electrodes after having replaced
the nozzle (see illustration). A wrong position could cause ignition
troubles.
DESCRIPTION OF CONTROL PANEL
D
RWF 40
G
C
E
A
25
420010310200 MULTICALOR 300.1-400.1 PR/PR
A - reset key
B - operating lamps (orange=light-oil; green= gas)
C - selector:
OUT = loking of devoices for operating at intermediate outputs
UP
= operation at max. output
LOW = operation at min. output
= automatic operation
AUTO
D - ON/OFF switch
E - selector:
0 = STOP
1 = light-oil operation
2 = gas operation
3 = automatic operation
F - termal lock-out lamp
G - modulating unit RWF 40 (optional)
5 ÷ 6 mm