IO-Link-Interface (Fortsetzung)
Device-spezifische Parameter
Index
Name
Subindex
(dez)
(dez)
0x0057
Operating
0x01 (1)
(87)
Hours
0x02 (2)
0x00B4
SIO Output
0x01 (1)
(180)
Type
0x02 (2)
0x00B6
Switch
0x01 (1)
(182)
Counter
Settings
0x02 (2)
0x03 (3)
0x04 (4)
0x00B7
Switch
0x01 (1)
(183)
Counter
State
0x02 (2)
0x00B8
Time Delay
0x01 (1)
(184)
Function
Q1
0x02 (2)
(Pin 4)
0x03 (3)
0x00B9
Time Delay
0x01 (1)
(185)
Function
Q2 (Pin 2)
0x02 (2)
0x03 (3)
0x00BA
Debounce
0x01 (1)
(186)
Time
0x02 (2)
0x00BB
Sensor-
0x00 (0)
(187)
Principle
0x00BC
Pin
0x01 (1)
(188)
Function
Selection
0x02 (2)
0x0421
Dark
0x00 (0)
(1057)
Measure-
ment
0x0422
Integration
0x00 (0)
(1058)
Time
0x0423
Maxpixel
0x00 (0)
(1059)
www.balluff.com
Name
Daten -
Zugriff
format
Operating
UINT32
Hours
Operating
Hours
Individual
Q1
UINT8
Q2
Mode
UINT8
Limit
UINT16
Unused
UINT16
StartupDelay
UINT8
Status
UINT8
Counter
UINT16
Delay Function
UINT8
Mode
Delay Time 1
UINT16
(On delay)
Delay Time 2
UINT16
(Off delay,
One shot)
Delay Function
UINT8
Mode
Delay Time 1
UINT16
(On delay)
Delay Time 2
UINT16
(Off delay,
One shot)
Pin 4
UINT16
Pin 2
UINT8
Pin 4
UINT8
Pin 2
UINT8
UINT16
UINT16
Wertebereich
R
R/W
0x01 (1) = PNP
0x02 (2) = NPN
0x03 (3) = PushPull
R/W
0x00 (0): Off
0x01 (1): Counter Static
0x02 (2): Counter Auto
0x0001...0xFFFF (1...65535)
0
0x00...0xFF (0...255)
R
Bit 0: Count Limit OK
Bit 1: Count Limit Too Low
Bit 2: Count Limit Too High
R/W
0x00 (0) = Delay
0x01 (1) = One shot
R/W
0x0000...0xFFFF (0...65535)
0 = Timing Function off
R/W
0x0000...0xFFFF (0...65535)
0 = Timing Function off
R/W
0x00 (0) = Delay
0x01 (1) = One shot
R/W
0x0000...0xFFFF (0...65535)
0 = Timing Function off
R/W
0x0000...0xFFFF (0...65535)
0 = Timing Function off
R/W
0 = Timing Function off
0x0000...0xFFFF (0...65535)
0 = Timing Function off
R/W
0x00 (0) = Background
Suppression
0x01 (1) = Background
Evaluation
R/W
0x00 (0) = Sensor Output/
Counter Output
0x00 (0) = Sensor Output
0x01 (1) = Reset Input
R/W
0x00 (0) = Disabled
0x01 (1) = Enabled
R/W
0x0001...0x02A8 (1...680)
R/W
0x0000...0xC000
(0...49152)
Bemerkung
Kann über Sys-
temkommando
Reset Operating
Hours zurückge-
setzt werden
Im SIO-Modus
Sekunden
Millisekunden
Millisekunden
Millisekunden
Millisekunden
Entprellzeit
Reseteingang
(Millisekunden)
deutsch
11