Installation manual
1
[°F]
[kΩ]
-40
336.5
-31
242.6
-22
177.0
-13
130.4
-4
97.1
Table 1 Sensor resistance table
Positioning of the outdoor sensor
For best performance the outdoor sensor is to
be positioned where the sun can never reach
it. Mount only on a North facing wall of the
building out of the sunlight, with at least 1 foot
above snow line. Keep the sensor away from
heat sources like dryer, water heater, or boiler
vents, windows, etc.
Fig. 6
Sensor location
6
[°F]
[kΩ]
5
72.9
14
55.3
23
42.3
32
32.7
41
25.4
☺
AM10 - We reserve the right to make any changes due to technical modifications!
[°F]
[kΩ]
50
19.9
59
15.7
68
12.5
77
10.0
86
8.1
[°F]
[kΩ]
95
6.5
104
5.3
113
4.4
122
3.6
☺