specify end positions
→
R
The GREEN LED lights up 2x.
All positions are now saved.
→
9.3.3. normal operation
Display normal operation
→
Switch on card.
The GREEN LED lights up 3x to indicate that the start
G
process has been implemented correctly.
In normal operation the GREEN LED lights up when the
G
rotary actuator opens the shut-off valve.
The RED LED lights up when the rotary actuator closes
R
the shut-off valve.
If neither of the LED's is lit, the actuator is not actuated.
G
R
The RED and the GREEN LED's light up if the torque
is too high and the rotary actuator stops.
→
G
R
Change direction of rotation of the rotary actuator
or switch over the voltage OPEN/CLOSED to
restart the rotary actuator!
26
Press <MEM> and <OPEN> push-
buttons to save the open position.
Disconnect the card from the power
supply.
english
Type 3005
Start-Up
10. start-up
Warning!
Danger due to improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
• In particular observe the safety instructions and intended use.
• The device/the system may be started by adequately trained
personnel only.
Procedure:
→
Ensure that connections and settings are implemented properly
according to chapter "8. Installation".
→
Check whether the rotary actuator and the fitting are in a defined
end position, otherwise the fitting may lock. In this case the
actuator switches off automatically.