jumper k1
trans-
feedback
ducer
a
0 - 10 V
0 - 10 V
ON
0 - 10 V
0 - 20 ma
ON
0 - 10 V
4 - 20 ma
ON
4 - 20 ma
0 - 10 V
OFF
4 - 20 ma
0 - 20 ma
OFF
4 - 20 ma
4 - 20 ma
OFF
4 - 20 ma*
0 - 10 V
ON
4 - 20 ma* 0 - 20 ma
ON
4 - 20 ma* 4 - 20 ma
ON
* Version with emergency reset
24
plug-in
plug-in
jumper k2
plug-in
jumper
b
a
b
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
english
9.3.2. parameterization steps
specify direction of rotation of the shut-off valve
normal direction of rotation (preset)
k3
OFF
G
OFF
ON
OFF
reverse direction of rotation
OFF
ON
OFF
R
OFF
ON
specify control signal type
control signal when voltage 0 – 10 V
R
Type 3005
Installation
→
Press <OPEN> push-button and switch on the
card (hold down push-button).
The GREEN LED lights up.
→
Release <OPEN> push-button and disconnect
the card from the power supply.
→
Press <CLOSE> push-button and switch on
the card (hold down push-button).
The RED LED lights up.
→
Release <CLOSE> push-button and dis-
connect the card from the power supply.
→
Press <MEM> push-button and switch
on the card (hold down push-button).
The RED LED lights up 3x.
→
Release <MEM> push-button and dis-