Check on the type label of the rotary actuator whether the
indicated voltage corresponds with the mains voltage.
Cables with a diameter of 7 to 12 mm are permitted for
the electrical installation. The utilized cables must have an
upper limit temperature of at least 80 °C.
preparatory work:
Remove stainless steel screws 3 for the hood 2 and carefully
remove the hood (see "Fig. 1" to "Fig. 3").
9.2.1. earth connection on outside or inside
The earthing cable for the power supply and control must be attached
with the earthing screw 16 (M5) to the outer body (see "Fig. 1" to
"Fig. 3").
procedure:
Loosen earthing screw 16 and attach eyelet of the earthing cable
with the earthing screw (see "Fig. 1" to "Fig. 3").
Optionally the earthing screw can be connected to Pos. A of the
power supply card.
To do this, loosen earthing screw and attach eyelet of the earthing
cable with the earthing screw.
Type 3005
Installation
9.2.2. 1 00-240 V ac (100-350 V Dc) or
15-30 V ac (12-48 V Dc) standard
version
The power supply voltage of the actuator is 15-30 V AC
(12-48 V DC) or 100-240 V AC (100-350 V DC).
Always observe the specifications on the type label!
H
B
A
C
Fig. 16: Power supply circuit board 15-30 V 50/60 Hz
(12-48 V DC)