Optional Components; Balancer Or Differential Pressure Valve - meibes LogoPack C Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

9. Optional components

9.1 Balancer or differential pressure valve

The balancer is used for the hydraulic balancing, i.e. to maintain the necessary differential pressure for the
hot water preparation in every supply line of the heating system. Meibes recommends using the Meibes Balancer DN 32 with partner valve
as a differential pressure regulator set.
Note: A maximum of 5 stations can be balanced in one line using this balancer. A larger difference pressure regulator, e.g. Ballorex Delta
(see price list) must be used for more than 5 stations.
• Remove the protective cap (black).
• Adjust the spring setting by screwing the spindle in or out with an open-ended wrench (6 mm).
• Screw on the protective cap.
Technical data for Meibes Balancer Set DN 32
Max. permissible operating pressure:
Max. permissible temperature:
Max. differential pressure over valve:
Differential pressure or control range:
Note: The line must be filled so that the pressure in the supply line is not considerably higher than that of the return flow, otherwise the
balancer valve will close.
Setting curves for Meibes Balancer DN 32
0,50
0,45
0,40
0,35
0,30
0,25
0,20
0,15
0,10
0,05
0,00
0,00
200,00
400,00
BALORE32.XLS
10 bar (1000 kPa)
+120 °C
2 – 4.5 bar (200 – 450 kPa),
on the largest with low flow
0.1 – 0.4 bar (10 – 40 kPa)
Balancer G (DN 32)
600,00
800,00
1000,00
1200,00
vom Balancer einzuhaltender Volumenstrom [l/h]
Einstellkurven
1400,00
1600,00
1800,00
2000,00
Federeinstellung
9
8
7
6
5
4
3
2
1,5
2200,00
2400,00
2600,00
2800,00
3000,00
18.06.2014
27