Connection
Connection Notes
•
Before opening the lid, ensure there are no dust deposits around the SITRANS LPS200.
Ensure that the atmosphere around SITRANS LPS200 is settled.
•
Use a fuse for the signal output (max. 6 A).
•
Make sure the main voltage does not exceed the maximum voltage listed on the
product label and the setting of the voltage selector.
•
In case of inexpert handling or handling malpractice, the electric safety of the
device cannot be guaranteed.
•
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
Switching Logic
7 6 5
Page EN-10
7
6
5
alarm output
relay
SITRANS LPS200 – INSTRUCTION MANUAL
M
1
2
N
L
115 V AC, 50 to 60 Hz, 4 VA
230 V AC, 50 Hz, 6 VA
or:
+
–
24 V DC, 2.5 W
All voltages ± 15 %
7 6 5
7ML19985FS61