4.4.2. ECOFLAM BURNER
• Open the box containing the diesel burner, remove it and keep the
two stickers with lot number for later use;
• Secure the burner plate to the machine by using the 4xM8 screws;
• Insert the burner and fix it to the plate by tightening the nut supplied
onto the central screw;
• Locate the black cable with 7-pin Wieland plug running out of the
electrical panel and insert the plug into the socket H on the burner;
• The ECOFLAM burner is factory-set according to the data shown on
the Technical Specifications Table in the User Manual.
Warning
The diesel burner is factory-set according to the
parameters shown on the "TECHNICAL SPECIFICATIONS
TABLE" for 50Hz models.
For 60Hz models, you have to change the combustion air
setting as shown on the Table.
4.4.3. DIESEL FILTER
• Remove the diesel filter and its bracket and secure the bracket to
machine wall using screws;
• Remove the nipple and, after wrapping the threaded portion to be
inserted into the filter with Teflon, screw it all the way down;
L
Warning
The threaded portion with internal conical chamfer M must
protrude in order to allow seal tightening with the hose.
• Screw the flexible suction hose of the pump onto fitting M on the
diesel filter unit.
• Screw the flexible supply pipe of the pump onto the second through
nipple.
• Close the burner cover;
• Apply one of the two stickers with the serial number on the
nameplate of the machine characteristic data:
L-L 278.00-SO
M
EN
• Apply the second sticker with the serial number on the Assembly
and Installation Declaration contained in the user manual:
4.5. CONNECTION TO FUEL SUPPLY
Warning
The heater must be installed, set up, and used in
compliance with all applicable regulations.
Connection to the diesel supply pipe can be made by connecting the
fuel tank to the burner pump:
• directly, i.e., by using the burner's diesel pump, in conformity to the
dimensions and lengths specified in the burner instruction manual
attached hereto.
• indirectly, i.e., by using an auxiliary return diesel pump. In this case,
contact a Customer Service Centre to ensure correct sizing of the
fuel system.
4.4. CONNECTION TO EXHAUST DUCT
Exhaust ducts must be in steel and conform to EN 1443.
Efficient combustion and trouble-free working of the burner depend
on efficient flue draft.
The unit must be connected to the chimney flue in compliance with
current legal regulations and in line with the following guidelines:
• The path of the flue pipe smoke should be as short as possible and
should slant upwards (minimum height 1 m);
• There should be no sharp curves in the pipes, and the diameter of
the pipes must never be reduced;
• there must always be a wind deflector to prevent the entrance of
rain and to prevent smoke from being blocked by the wind;
• flue draft must at least equal the level in the Technical
Specifications.
• every heater must have its own chimney;