Approvals
(valid for marked equipment)
PY X-L-15 + PY X-LA-15
Rated Voltage
Amb. Temp.
UL, cUL
115 V AC
230 V AC
24 V AC
24 V DC
PYRA Xenon beacons PY X-L(A)-15 comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Taking into Operation
Safety notes:
Life-threatening danger due to electric shock
-
Before all work on the equipment, the following should be observed:
Switch off the power supply before opening.
-
Wait 5 minutes before opening the housing
DANGER
-
All work on the equipment is only to be carried out by authorised technical personnel in accordance
with all applicable regulations.
-
The operating voltage may only be applied if the housing is tightly closed.
Danger of injury due to sharp edges or heated components
-
It is recommended to wear gloves during installation, assembly, or service / maintenance work.
-
In order to prevent detriment to sight, continuously looking directly in the activated light is to be
CAUTION
avoided.
- Before electrical connection, the supply voltage on the type plate is to be checked. The wrong operating voltage can lead to
damages or to the destruction of the equipment.
- During installation it must be ensured that the connection cables are secured against tension and distortion.
Please observe: The devices are not designed for portable use.
- CAUTION: When making installation, route field wiring away from sharp projections, corners and internal components.
- The function of the unit is only guaranteed if the upper and lower section is joined correctly.
- DC voltage: The device is provided with a reverse polarity protection. No function when polarity is reversed!
Opening the housing
1.
2.
3/8
The unit is not closed when delivered. Sealing plugs for the housing screws are available as accessories.
085 501 995c
Visual Signal Appliance - General Signaling Equipment (UEES, UEES7) (PY X-L-15)
Audible and Visual Appliance for General Signaling (Non Fire Alarm) Use
(UCST, UCST7 and UEES, UEES7) (PY X-LA-15)
115 V AC or
230 V AC or
24 V DC / 24 V AC
-40°C .. +66°C
Suitable for indoor and outdoor use.
Warning: Not to be used as a Visual Public Mode Alarm Notification Appliance.(PY X-L-15)
Warning: Not to be used as an Audible and Visual Public Mode Alarm Notification Appliance.(PY X-LA-15)
According to CSA-C22.2 No. 205-12 clause 4.3.4 the connection is limited to max. 10 leads.
Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer's installation instruc-
tions as well as the National Electrical Code (NFPA 70) in US. In Canada, they shall be installed in accord-
ance with the Canadian Electrical Code, Part 1. The installations shall also be in a manner acceptable with
the local authority having jurisdiction.
Cable gland entries:
Conduit installation needs to be UL/ cUL listed fittings suitable for knockout openings.
By loosening the four cover
screws, the upper section
can be removed.
(
)
Closing the housing
1.
2.
3/8
6
The housing is closed by
turning the cover screws to
the limit position until the
housing locks into place.
(
)