Télécharger Imprimer la page

STEINEL PROFESSIONAL IR Quattro COM1-WR Manuel page 23

Publicité

Les langues disponibles

Les langues disponibles

Remote Control
Using the remote control,
functions can be conveniently
activated from the floor.
RC 3 Service Remote
Description
The RC 3 service remote (commissioning tool) gives the
installer the ability to set basic functions of the entire line
of Control Pro sensors via remote control. Each valid press
of a button is indicated by a blue LED flash on the sensor.
4
5
8
10
11
Functions
Reach setting (Control Pro Ultrasonic and
Dual tech sensors only)
Ultrasonic coverage can be selected from mini-
1
mum, 1/3, 2/3, or maximum by pressing these
buttons. Use this setting to increase or decrease
the coverage (detection range) of the sensor.
Time setting CH 1
Stay 'ON' time for switching contact 1
The period of time you want the light to stay 'ON'
2
for after last detecting movement can
be set from between 30 sec., 2 min., 5 min.,
15 min. and 30 min. by pressing these buttons.
IR Quattro COM-WR_USA_03-07-13_ENU-FRA.indd 23
R Quattro COM-WR_USA_03-07-13_ENU-FRA.indd 23
Note: The pulse mode cannot be
overridden by the remote control.
Switch pulse mode 'OFF' manually.
-
Presence Control remote
control unit:
- RC 3 Service Remote
- RC 4 User Remote
Setting the light to stay 'ON' for a time of your
3
own choice. Each press of the button increments
the chosen time setting by 1 minute.
IQ mode. Stay 'ON' time is self-learning and
4
adjusts dynamically to user behaviour.
The optimum time is determined by means of a
1
learning algorithm. The shortest time is 2 min.,
the longest time 20 min.
Test mode. The test mode has the purpose of
5
checking for proper working order as well as
testing the detection zone. The presence detec-
2
tor switches 'ON' for approx. 8 sec. regardless of
brightness and movement. The test mode has
3
priority over all other settings. All user-selected
potentiometer settings apply in normal mode.
The test mode ends automatically after 10 min.
Time setting CH 2 -
6
Stay 'ON' time for switching contact 2 (HVAC)
The period of time you want the HVAC contacts
6
to signal the HVAC controller (stay 'ON') after
7
last detecting movement can be set from 1 min.,
5 min., 30 min., or 2 hours by pressing these
buttons.
Light level setting
9
The chosen response threshold can be varied
7
from approx. 10 – 1000 lux / 1 - 100 fc.
Night-time mode (minimum setting
8
12
approx. 10 lux. , 1 fc.)
Daylight mode (maximum - light level function
9
overridden)
Teach-IN. Twilight setting at the memory but-
10
ton/Teach mode. This button must be pressed at
the level of light at which you want the sensor to
respond to movement. The current light level is
saved.
Sensor sensitivity (Ultrasonic and Dual tech only)
Ultrasonic sensitivity can be reduced by pressing
11
the button
sensitivity. Use this setting to adjust the amount
of motion required within the detection area
before the sensor will trigger.
Reset
Resets all settings to the values selected on the
12
detector manually or to the factory settings.
- 23 -
. The button
restores normal
04.07.13 14: