Technical Data / 24 month Warranty
Resolution ......................................1ms
Tolerance ........................................± (2%+2Digit)
Display ............................................0...70 V
Resolution ......................................0,1 V bei IΔN 100, 300, 500, 1000mA
........................................................1V bei IΔN 10, 30mA
Tolerance ........................................-0%...+10% /+6 Digit
Limits .............................................25V / 50V, contact voltage limit UL to be pre-selected
Auto function
Measurement ranges .....................10, 30, 100, 300, 500, 1000mA idem
........................................................100, 300, 500, 1000 mA selective
Test currents ..................................0.5 x IΔN,
........................................................1 x IΔN,
........................................................2 x IΔN,
........................................................5 x IΔN (not at IΔN = 500 / 1000 mA standard or S ),
........................................................automatic selection, also refer to table 1
Phase position ................................0° / 180°, automatic selection
Measurement time ..........................see table 3, when exceeding limits, immediate cut-off
Display ............................................O.K. / bad ( POS / Err )
Limits .............................................25V / 50V, contact voltage limit UL to be pre-selected
Mains Voltage Range
Measurement range ........................3...300V AC
Tolerance ........................................+/-(3%+3 Digit)
Frequency range .............................50/60Hz +/- 10%
Internal resistance ...........................approx. 300kΩ
Overvoltage protection ....................400V AC/DC

24 month Warranty

UNITEST instruments are subject to strict quality control. However, should the instrument function impro-
perly during daily use, your are protected by our 24 months warranty (valid only with invoice).We will
repair free of charge any defects in workmanship or material, provided the instrument is returned unope-
ned and untampered with, i.e. with undamaged warranty label.Any damage due to dropping or incorrect
handling are not covered by the warranty. If the instrument shows failure following expiration of warranty,
our service department can offer you a quick and economical repair.