General Information About Rcd Tests - BEHA UNITEST TELARIS Fi/RCD Mode D'emploi

Masquer les pouces Voir aussi pour UNITEST TELARIS Fi/RCD:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Proof regarding the low impedance connection of
equipotential bonding conductors in compliance
with Section 5.4 must be available.
Any test and measurement procedures in cir-
cuits equipped with residual current devices
should only be performed after having consult-
ed the operator terminals (data processing sys-
tems, material processing, motors, etc.).
Prior to testing, we recommend all loads are
switched off as they could falsify the measure-
ment result.
The protective earth must be free of external
voltage for the RCD test. However if an extra-
neous voltage is present, the instrument only
indicates the voltage VC having been generated
by the measurement. The measurement inter-
ruption caused by excess of UL by VC is only
generated by the actual voltage present be-
tween the neutral conductor (N) and the pro-
tective earth (PE).
Time-delayed residual current devices trip at
nominal residual current within 130...500ms,
for double nominal fault current within 60...200
ms. Such RCDs are implemented as main resid-
ual current protection devices (please refer to
IEC 61008-1) and are marked with the symbol
" S ".
The contact voltage represents the voltage pre-
sent during an insulation error between two si-
multaneously touchable components.
At a measuring circuit without probe, available
voltages between PE and earth can influence the
measurement.
Before using the N-conductor as probe check
that all neutral points have low ohm resistance
to the main neutral line. A available voltage of
the N conductor to the arth can influence the
measurement.

General Information about RCD Tests

The measuring function uses the N-conductor
as a probe. Check first the connection between
the neutral point of the distribution system and
earth before the test is started. A possible volt-
age between the N-conductor and earth may in-
fluence the measurements.
Leakage currents in current circuits following
the RC circuit breaker may have an influence
on the test as well as a voltage between pro-
tective conductor or neutral conductor and
ground.
Attached loads or operating supplies which
contains capacitors or circulating machines
can elongate the trip time.
Measurements may be influenced by potenti-
al fields of other grounding systems.
(FAT) measurements must be carried out in
compliance with the respectively valid stan-
dards and regulations.
37

Publicité

Table des Matières
loading

Table des Matières