Télécharger Imprimer la page

Comelit 41LED032 Manuel Technique page 9

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ADDRESS PROGRAMMING
CONNECTION DIAGRAMS
a) Wiring of LED Outputs
1.
Common-anode circuit type; "CA/CC" jumper is removed, Ri = 1kΩ or Ri = 0kΩ.
2.
Common-cathode circuit type; "CA/CC" jumper is set, Ri = 1kΩ or Ri = 0kΩ.
Power off the module before setting/removing the "CA/CC" jumper for selection of the circuit type for wiring of the LED outputs! The
setting/removing the jumper, when the power is on will not change the circuit type!
b) External Power Supply Connection
c) Loop Connection
d) Wiring of special LED Outputs
LED Outputs "FIRE", "FAULT", "DISABLEMENT" (for repeating events from fire alarm control panel) and "POWER ON" (for indication of
power supply presence of the connected to the module mimic/repeater panel) are wired in the same way as described for LED Outputs
1-32.
e) LED Indication of Module's Status
YELLOW, lighting ОN – no external power supply 12-24VDC connected to the module;
RED, lighting ON – device is selected from the control panel, the LED is manually Turned ON to find out the local place of the module;
RED, slow blinks at 10 sec. interval – communication with the control panel, normal operation mode.
Use the cable with 5-pin terminal.
The built-in isolator is used

Publicité

loading