Télécharger Imprimer la page

Comelit 41LED032 Manuel Technique page 6

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ATTENTION: Read carefully this installation Instructions before installing the device! This manual is subject to
change without notice! The addressable module 41LED032 must be connected only to fire panels supporting Comelit
communication protocol!
INSTALLATION INSTRUCTIONS
Operation with 41LED032 addressable module is supported for the following and higher SW revisions of fire alarm panels: LogiFire
41CPE118 - 1.0.x; LogiFire 41CPE112 and Atena Easy 41CPE012 - 4.3.x; Atena 41CPE024 - 6.3.x!
The maximal number of used 41LED032 modules per system configuration, depends on the type of the fire alarm control panel:
LogiFire 41CPE118 – up to 50 pcs.; LogiFire 41CPE112 and Atena Easy 41CPE012 – up to 5 pcs.; Atena 41CPE024 – up to 10 pcs.
General Description
41LED032 is an addressable module, specially designed for connection to mimic/repeater panels presenting a geographical plan of
the fire alarm system. The module is capable to control up to 32 LED outputs for indication of different events in the fire system, and
is provided also with special LED outputs for repeating a FIRE Alarm, Fault and Disablement events directly from the fire alarm control
panel.
The module has a built-in isolator module which when used allows continuous operation of the loop in case of module's failure and
without need of using additional isolator modules.
This module must be powered on from an external power supply unit 12-24VDC.
The module is delivered mounted into a plastic box suitable for wall mounting with IP43 rating. It is recommended to use it only for
indoor installations.
The 41LED032 module PCB can be mounted also directly into the installation box of the mimic/repeater panel.
Wiring Types
The LED outputs of 41LED032 module can be wired as Common-Anode (CA) or Common-Cathode (CC) circuit type. The type of
the circuit is set via jumper "CA/CC" on the PCB. The "Common-Anode" circuit type is selected when the jumper is removed; the
"Common-Cathode" circuit type is selected when the jumper is set. The required compensating resistors (Ri) are built-in (SMD
mounted). Their value is common for all LED outputs. The wiring circuit types are presented into Connection diagram section.
Important Note: Power off the module before setting/removing the "CA/CC" jumper for selection of the circuit type for wiring
of the LED outputs! The setting/removing the jumper, when the power is on will not change the circuit type!
Operation Access Levels of the Inputs
The 41LED032 module is provided also with 4 special inputs for user operation, organized in 2 access levels. The Level 1 is giving
access for operation with the module itself: Silencing of the internal buzzer (via the "Sil. BUZZ" input) and testing the operation of LED
outputs and buzzer (via the "TEST" input).
The Level 2 is active after activation of the "Key Switch" input (via two-position key switch, latch push button, etc).
At Access Level 2 are accessible the operations mentioned above for Level 1 and also the following controls of the connected fire alarm
panel: Silencing of the sounders in case of Fire Alarm at the protected site (via the "Sil ALARM" input) and resetting the fire panel (via
the "RESET" input).
Installation
Attention: Power off the loop circuit before installing the 41LED032 addressable module!
1.
Choose the proper place for installation. The module can be mounted directly into the installation box of the mimic/repeater panel
(PCB only) or to be placed in a single box next to the controlled equipment (up to 3m).
2.
Set the module's address using the 41SPG000 Programmer or set it directly from the addressable fire alarm panel. The address
must be in range from 1 to 250. The set address is one for the entire module.
3.
Set the connection circuit type for the LED outputs*:
- Common-Anode, jumper "CC/CA" is removed (OFF), Ri=1 kΩ or Ri=0 kΩ.
- Common-Cathode, jumper "CC/CA" is set (OFF), Ri=1 kΩ or Ri=0 kΩ.
4.
Run the cables to the module terminals.
5.
Connect the LED Outputs according the selected circuit type*.
6.
Connect the loop wires.
7.
Connect the Inputs and Specialized LED Outputs.
8.
Connect the external power supply unit as observe the polarity: red wire to the "+PW" terminal and the black wire to the "-PW"
terminal.
9.
Power on the module - switch on the external power supply and the loop circuit.
10. Test the module for proper operation and LED indication.
* It is possible the circuit type to depend on the used connection in the connected mimic/repeater panel.

Publicité

loading